1SERIES16CTEMPERATURE/PROCESS CONTROLLERInstruction Manual (Basic Operations)
67OperationMode/Enter KeyUsed to enter Parameter selections, access operating modes, release latched alarms, and index through menu items.Lower KeyUse
67Power OnWhen power is first applied to the Series C, all segments of the LED displays will be momentarily illuminated while the instrument goes thro
8 Security LevelsThe security level feature allows you to limit access to the menus, setpoint, and operating mode selection according to the needs of
89Operating Modes The Series C’s operating modes are: Manual, Standby, Normal, Autotune, Ramp/Soak Recipe, Run and Hold. To select a different operati
1011Menu System Overview The Parameter Menu System is organized into ten basic menus: Input, Display, Output, Control, Alarm, Tune, Recipe, Supervisor
1011Menu System OverviewFigure 10. Series C Functional DiagramTo return to Process Value at any time, press and hold Menu Access key for three secon
12Menu System Overview Figure 11. Chart of Series 16C Menu System and Security Levels(Continued on Next Page)Mode/ Enter KeyMenu Access Key(number)(n
Security Levels (Key Lockout) = No Access (Setpoint) = Setpoint Value or Output Percentage (Manual
Input Used to select sensor-related parameters, such as input type, limits, and scaling. Display Used
15NOTE: FOR A MORE DETAILED DESCRIPTION OF MENU PARAMETERS, REFER TO THE GLOSSARY WHICH BEGINS ON PAGE 64.The first par
3 IntroductionPrecautionsCongratulations on your purchase of an Athena Series 16C Temperature/Process Controller. It is designed for ease of use and
17Input Type JMPØ1 JMPØ2Thermocouple Out OutRTD Out OutVoltage <100 mV
17Display MenuJMPØ1Display Parameter Selection Decimal Position 0-3 Linear Inputs
1918Output Menu Output 1 Action Reverse-acting (Heating) Direct-acting (
19Output Menu Control Menu Display Parameter Selection Output 1 Action Reverse-acting (Heating)
2021Notes On AlarmsOutputs can be set up as an alarm, similar to the standard alarm format. Four types of alarms are available: Process, Deviation, In
2021Output Menu Display Parameter Selection Output 1 Alarm Action
22Display Parameter Selection Damping Low
2223Recipe (Ramp/ Soak) Menu Power Fail ResumeSetting this parameter to On will cause the control to resumea recipe which was active when a power fail
2524NOTE: The following seven parameters are only available whenmulti-step ramp is selected.Display Parameter Selection Recycl
25 Toggles with the temperature value that should be input to perform the low calibration operation. The low calibration operation is
3In addition to presenting a potential fire hazard, high voltage and high temperature can damage equipment and cause severe injury or death. When inst
2627 AutotuningTo place the controller in Autotune mode:1) Configure the controller by following the directions for Initial Setup Sequence through St
2627AutotuningIf a tune error condition occurs, the upper display will toggle between and a numeric error code for three seconds before the tune pro
28Manual Tuning Manual Tuning Procedure(Zeigler-Nichols PID Method)This tuning method may be used for non-temperature control processes or if the spr
2829Error CodesIf an error code cannot be cleared by using the actions provided, contact factory.Display Problem
30Technical Specifications Operating Limits Ambient Temperature 32°F to 140°F (0°C to 60°C) Relative Humidity Tolerance 90%, N
3031Technical Specifications Input Type Thermocouple B, C, E, J, K, N, NIC, NNM, R, S, T, Platinel II Maximum lead res
3233Ordering Codes Code Input Type CT Thermocouple CR RTD CS Compressed RTD CM Millivolt Li
3233The Series C controller is precalibrated at the factory. Under normal circumstances, the factory calibration should be valid for the life of the i
34Quick-Helps1. To return the unit to last operating mode (Normal, Standby, FOP, or Tune): Action
3435Quick-Helps 5. To abort Autotuning Action Display and return to normal Press and hold
41Table of ContentsInstallation 1Dimensions and Mounting
36Warranty/ Repairs Two-Year Limited WarrantyTHIS EQUIPMENT IS WARRANTED TO BE FREE FROM DEFECTS OF MATERIAL AND WORKMANSHIP. IT IS SOLD SUBJECT TO OU
37Warranty/ Repairs Unit RepairsIt is recommended that units requiring service be returned to an authorized service center. Before a controller is ret
3839IECRequirementsThe maximum supply current is line voltage dependent:230 mA for a 24 Vac/dc input fuse rating=700 mA60 mA for an 85-250 Vac
3839Alarm Delay - the time delay between the detection of the alarm condi-tion and the initiation and indication of the output action.Alarm Inhibit
4041input failure, or a heater or load failure.Loop Break Time - the time interval from when the controller detects a loop break condition and the ini
4041Quick Setup Instructions - Series 16C Temperature ControllerExperienced users, already familiar with the Series 16C, and using the controller with
4243Keep This Information in a Safe PlaceConfigured Parameters Reference Data Series C Temperature Controllers Model Number Zone Location Firmware
4243Notes
44Athena Controls, Inc.5145 Campus DrivePlymouth Meeting, PA 19462 U.S.A.Tel: (610) 828-2490Fax: (610) 828-7084Toll-Free in U.S.: 1-800-782-6776Intern
41InstallationMeasurements between centerlines of panel cut-outs are the minimum recommended.Unpacking and Inspection1. Inspect shipping carton for o
23MountingDimensionsFigure 2. Case DimensionsPrior to mounting the Series C in your panel, make sure that the cutout opening is of the right size, 1.7
23WiringIMPORTANT: All electrical wiring connections should be made only by trained personnel, and in strict accordance with the National Electrical C
4WiringFigure 5. Thermocouple Input Wiring Make sure that you are using the appropriate thermocouple and extension wire. Connect the negative lead (ge
45Output TypesThe Type “B” output is a mechanical device and subject to wear. To extend the life of the relay, set the Cycle Time for the relay output